Feature
Splice and terminate cables, emergency overload temperatures up 266°F (130°C)
Poly-isobutylene (PIB) tape
Physical and electrical properties are unaffected when the degree of stretch
Self-fusing(Adhesive)tape
Liner not stick on tape
Compatible with all solid dielectric cable Insulation as Polyethylene, XLP, PVC, Butyl Rubber, EPR and Oil-based rubber
Application
Primary electrical insulation for splicing cable from 600 V to 15kV on all solid dielectric cables
Primary insulation for building stress cones up to 10kV on all solid dielectric cables
Medium-voltage splices Jacketing and terminations
Moisture sealant electrical connections
Bus bar insulations
End sealing high-voltage cables
Color
● Black
Dimension
Width | Thickness | Length | |
19mm(3/4 in) | 0.76mm(30mils) | 9.15m(30 ft) | |
25mm (1 in) | 0.76mm(30mils) | 4.5m(15 ft) | |
38mm (1.5 in) | |||
50mm (2 in) |
Package
● 100 PCS/Carton
Specification
Index | Typical Value | Test Method | |
Tensile Strength | 1.86 MPa | ASTM D 4325 | |
Elongation | 769% | ASTM D 4325 | |
Di-electric Strength | 32.9kV/mm | ASTM D 4325 | |
Di-electric Constant | 2.82 | ASTM D 4325 | |
Self-adhesion | Ⅲ Pass | ASTM D 4388 | |
Heat Exposure(130℃/168H) | Pass | ASTM D 4388 | |
Ozone Resistance | Pass | ASTM D 4325 | |
Ultraviolet Radiation Aging | Pass | ASTM D 4325 | |
Xenon Lamp Aging | Pass | ISO4892-2 | |
Normal Temperature | 90℃(194℉) | ||
Emergency Temperature | 130℃(266℉) |
*All these data are typical value
Warranty & Storage
● 5-year shelf life from date of manufacture
● 10°C/50°F to 27°C/80°F storage temperature
● <75% relative humidity